The digital RCD tester is used to test and measure the function parameters of residual current devices (RCDs) in 230-V power grids. Both the trigger time and the tripping current can be detected as the safety-related parameters of RCD switches
| Power supply | 4 x 1.5-V alkaline battery (AA/LR6) |
| Testable C/B switch | normal/delayed, AC/A |
| Power grid | 230 V (-10%/+6% ), single phase, TT/TN, 50/60 Hz |
| Warning function | grid 400 V, error voltage (contact voltage) >50 V |
| Test currents | 10-30-100-300-500-650 mA |
| Test current accuracy | ±(10%+2 digits) |
| Test time | 0 - 300 ms |
| Test time accuracy | ±(5%+3 digits) |
| Ramp test | delta 0.4 to 1.1 with the set error current, accuracy ± 10% |
| Display scope | 3 digits with backlight |
| Protection class | IP 40 |
| Safety | IEC61010 CAT III (600 V), double insulated, IP40 |
| Dimensions (W x H x D) | 71 x 210 x 51 mm |
| Weight | 340 g (including battery) |